Technical Data - Samson TROVIS 5724-8 Series Mounting And Operating Instructions

Electric actuator with process controller without failsafe action and with fail-safe action for heating and cooling applications
Hide thumbs Also See for TROVIS 5724-8 Series:
Table of Contents

Advertisement

Design and principle of operation
Accessories for sensors
− Mounting kit for a Pt 1000 cable sensor
as contact sensor, order no. 8524-0020
− Brass thermowell, G ½, immersion length
80 mm, PN 16, order no. 1099-0807
− CrNiMo steel thermowell, G ½, immer-
sion length 80 mm, PN 40, order no.
1099-0805

3.6 Technical data

Electric actuator with process
controller
Fail-safe action
Connection to valve
Rated travel
Transit time for rated travel
Stroking speed
Thrust
Supply voltage
Power consumption
Manual override
Permissible temperatures
Ambient
Storage
Degree of protection (not installed
suspended)
Electromagnetic compatibility
Connecting cable length
16
TROVIS
Actuator stem
 1)
− CrNiMo steel thermowell, G ½, immer-
sion length 250 mm, PN 40, order no.
1099-0806
− Brass thermowell, G ½, immersion length
160 mm, PN 16, order no. 8525-5005
− CrNiMo steel thermowell, G ½, immer-
sion length 160 mm, PN 40, order no.
8525-5011
5724-
5725-
5724-
810
810
820
With-
With-
With
out
Ex-
tends
Force-locking
6 mm
35 s
700 N
500 N
700 N
230 V (±10 %), 50 Hz
With-
With
With
out
0
–20
According to EN 61000-6-2, EN 61000-6-3 and
Two-wire, 5 m
5725-
5724-
820
830
With-
With
out
out
Ex-
tends
12 mm
70 s
0.18 mm/s
500 N
700 N
6 VA
With-
With
out
to
+50 °C
to
+70 °C
IP 54
EN 61326
·
Three-wire, 2.5 m
EB 5724-8 EN
5725-
830
With
Ex-
tends
Form-fit
15 mm
90 s
280 N
With-
out

Advertisement