CO/PA
Function/
designation
M ...
Actuator
Actuator parameters
MY.EA
End position guiding (stem
extends)
MY.EE
End position guiding (stem
retracts)
MY.TE
Idle time during end posi-
tion guiding
MY.TZ
Dead band (switching
range)
Signal failure
A7.1
Function
A7.YP.ERR
Fixed actuator positioning
value
Actuator
A8.1
Zero calibration
A8.2
Restart conditions
A8.3
Blocking protection
Characteristic
M6
Characteristic type
EB 5724-8 EN
Setting/
adjustment range
0.0 to 49.9 %
50.0 to 100.0 %
0 to 99 s
0.5 to 5.0 %
0:
Last travel value
1:
Fixed positioning value
0.0 to 100.0 %
0:
Extend actuator stem
1:
Retract actuator stem
0:
Start with last operating state
1:
Start with operating function [O]
2:
Start with operating function [I]
0:
No
1:
Yes
0: Linear
1: Equal percentage
2: Reverse equal percentage
3: User-defined
#
1
2
3
X
0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0
Y
0 10.0 20.0 30.0 40.0 50.0 60.0 70.0 80.0 90.0 100.0
4
5
6
7
8
Annex
9
10
11