Samson TROVIS 5724-8 Series Mounting And Operating Instructions page 44

Electric actuator with process controller without failsafe action and with fail-safe action for heating and cooling applications
Hide thumbs Also See for TROVIS 5724-8 Series:
Table of Contents

Advertisement

Annex
CO/PA
Function/
designation
Error signal
C1.3/C2.3
Function
PID controller
C1.KP/
Proportional-action coeffi-
C2.KP
cient
C1.TN/
Reset time
C2.TN
C1.TV/
Derivative-action time
C2.TV
C1.Y0/
Operating point
C2.Y0
Manipulated variable
C1.4/C2.4
Function
C1.YP/C2.
Fixed actuator positioning
YP
value
44
Setting/
adjustment range
0: Not inverted
1: Inverted by DI1
2: Inverted by DI2
3: Inverted by DI3
4: Inverted by DI4
5: Inverted by LIM1
6: Inverted by LIM2
7: Inverted
0.1 to 999.9
0 to 999 s
0 to 999 s
0.0 to 100.0 %
0:
Controller positioning value
1:
Fixed actuator positioning value with DI1
2:
Fixed actuator positioning value with DI2
3:
Fixed actuator positioning value with DI3
4:
Fixed actuator positioning value with DI4
5:
Fixed actuator positioning value with LIM1
6:
Fixed actuator positioning value with LIM2
0.0 to 100.0 %
EB 5724-8 EN