Hitachi Hidic EH-150 Applications Manual page 38

Ethernet module
Hide thumbs Also See for Hidic EH-150:

Advertisement

Preliminary Rev.03
Table 5.11 The list of items of Automatically Sending and Receiving I/O area configuration
No
Name
Receive area
1
I/O
2
Top
3
Size
Send area
4
No.
5
I/O
6
Top
7
Size
The contents of this manual might be changed without notice.
Chapter 5 Configuration and procedure for starting communication
Description
To specify the I/O for the receiving area. If there is no specifying (2)
and (3) are not valid.
To specify the starting I/O number for the receiving area.
To specify the I/O size (count of words) for the receiving area.
To specify the entry number. The entry number means the saving
order of the sending I/O area data in the sending message. This is
useful to change the I/O area order among the exist configuration.
Please specify this No. not to be duplex. (If the duplication is exist,
an error is detected.)
To specify the I/O for the sending area. If there is no specifying (6)
and (7) are not valid.
To specify the starting I/O number for the sending area.
To specify the I/O size (count of words or bits) for the sending area.
5-22
Range for setting
WY,WR, WL, WM
The range is same with
each I/O's ranges.
1 to 747(word)
1 to 10
X,Y,R,L,M,TD/CU,CL,
WX,WY,WR,WL,WM,
TC,DIF,DFN,TM,TV
The range is same with
each I/O's ranges.
1 to 11632 (bit type)
1 to 747(word type)