Preliminary Rev.03
4.1
Operating mode
Operation mode of EH-ETH is set by a dip switch on the front panel. The set operation mode is effective after
completion of EH-ETH initialization. There are 2 ways to start the initialization, one is from turning on power
and another is from executing Hardware and software reset.
Out view of the dip switch is shown in Fig. 4.1.1.
Regarding detailed Ethernet information setting refer to "5.2 Ethernet setting". And regarding detailed "self
diagnostic refer to "10.1 Test functions".
1
2
ON
ON
OFF
OFF *(*2)
*1: In case of setting lowest byte of IP address, OFF position of the switch means "0" and ON position means
"1".
Upper 3 bytes are fixed to "192.168.0". Therefore select one IP address temporally from "192. 168.0.1 to
192.168.0.63"
*2: "*" means don't care.
*3: Need loop back connector.
Caution
- Because IP "192.168.0.0" has a special meaning, all bit 3 to 8 should not be "0". If the bit 3 to 8 are all "0",
then LED's turn ON or flick as follows.
In case of SOFTWARE VER.00 to VER.02: The Status LED turns ON in red 6 times.
In case of SOFTWARE after VER.03: The Status LED tuns ON in red 7 times and the I.ERR LED
- IP address set by the dip switch is used temporally to access a Web server in side EH-ETH.
Therefore the IP address set by the dip switch is not saved in a FLASH ROM inside EH-ETH.
Contents of this manual may be changed without any
1
ON
Fig. 4.1.1 Out view of the dip switch
Table 4.1.1 Dip switch setting and operation mode
bit
3
4
5
6
7
Lowest byte of IP address (*1)
b'000001 to b'111111(1 to 63)
*
*
*
*
ON
OFF
turns ON in red at the same time
2
3
4
5
6
7
8
Operation mode
8
Setting Ethernet information by user program
IP address setting
Setting Ethernet information and ARS
mode
connection using general Web browser
ON
Test mode of SEND and RECEIVE data
Self diagnostic
OFF
External loop back check
mode
ON
Internal loop back check
Normal operation
OFF
For normal operation
mode
4-2