Self-Diagnosis Data Output By Xs770A - YOKOGAWA Sushi Sensor XS770A User Manual

Wireless vibration sensor functions
Table of Contents

Advertisement

Table 6-1
DIAG
Status
STATUS
Display
(Table
7-9)
No setting
Bit25
Unconnected
Bit25
OFF
Bit24
Low power Bit20
Bit19
Temperature
Bit22
error
In failure
Bit27
Bit26
Sim
Bit17
Threshold
Bit23
error
Good
6.3

Self-diagnosis Data Output by XS770A

XS770A sends the device status to the Data collection server once a day. Monitor the device
status by using this server if necessary. For details of health report information (HRI) and self-
diagnosis information (DIAG) refer to Section 7.
XS770A status and action strategies
DIAG
DATA_
STATUS
STATUS
Output
DETAIL
(Table
Operation
(Table
7-3)
7-10)
Bit23
-
Bit22
-
Bit16
-
Bit31
-
Normal
measurement
Bit30
-
Normal
measurement
Bit28
-
Normal
measurement
Bit29
Normal
measurement
Bit19
-
Normal
measurement
Bit25
Bit15
Previous
value
Bit14
Previous
value
Bit24
Bit13
Previous
value
Bit17
Bit8
Simulation
value
Bit21
Bit12
Normal
measurement
Bit11
Normal
measurement
Bit20
Bit10
Normal
measurement
<6. Operation and Maintenance>
Description
Network is not
Configure the network for
configured for XS770A.
XS770A. Refer to Section
5.1.
XS770A is not
Check whether there is any
connected to the
shielding object between
gateway.
XS770A and the gateway, or
any object that interferes with
radio waves.
XS770A is in OFF mode. Perform the procedure to
change ON mode (refer to
Section 6.9.2).
Power is low.
Replace the battery. Refer
to Section 6.7 for the battery
replacement procedure.
The battery life has
dropped to 25% or less.
CPU temperature goes
The XS770A operating
outside the specified
environment is outside the
range.
specified range. A failure
may occur if you keep using
it without taking corrective
actions. Use it in a location with
an environment that meets the
relevant specifications.
A memory error has
Replace the device. Back
occurred.
up the XS770A setting if
necessary.
An error has occurred
during acceleration
measurement.
An error has occurred
during velocity
measurement.
An error has occurred
during temperature
measurement.
Task check is running for
The simulation value is being
XS770A.
sent.
Wait until the task check is
completed.
The vibration value
Check the installation status
measured by XS770A is
of XS770A.
outside the measurable
range.
The temperature
measured by XS770A is
outside the measurable
range.
XS770A is in a normal
None in particular
state.
33
Action
IM 01W06E01-11EN

Hide quick links: