7 Periodic Actions
Disassembling the panels
1. Remove the screws of the front panels using a Torx screwdriver (head size T30).
2. Detach the grounding straps from the panels.
3. Remove the panels.
Mounting the panels
Requirement:
☐ The protective covers in the connection area must be mounted (see Section 7.2.2, page 42).
Procedure:
1. Attach the grounding straps to the panels of the interface cabinet (torque: 8 Nm to 10 Nm).
2. Ensure that the grounding straps are firmly in place.
3. Attach the panels using a Torx screwdriver (torque: 2 Nm to 3 Nm, head size T30).
7.2.2

Disassembling and Mounting the Protective Covers

Figure 11: Position of the protective covers
Position
Designation
A
Protective cover
42
SCCP-JP-B1-IA-en-21
SMA Solar Technology AG
Installation Manual