Appendix-1: Technical Specifications - LEGRAND Inform SINUS EVO User Manual

Table of Contents

Advertisement

Appendix-1: Technical Specifications

MODEL
Output Power Factor
INPUT
Input Voltage Range
Input Frequency Range
Phase
Power Factor
OUTPUT
Output Voltage
Voltage Regulation
Frequency
Frequency (@Battery Mode)
Overload
Crest Factor
THD
Online Mode - Battery Mod
Transfer
Period
Inverter- Bypass
Battery Mode Waveform
Outputs
ECO MOD
Frequency Converter
EFFICIENCY
Online Mode
Battery Mode
BATTERY
Battery Type
QTY
Charge Time
Charge Current
Automatic Battery Test
External Battery
Charge
Voltage
≧ 0.99 @ nominal voltage (input voltage)
110/115/120/127VAC or 208/220/230/240VAC
47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range)
105%~110%: 10 minute ,110%~130%: 1 minute, >130%: 3 second
≦ 3 % THD (linear load); ≦ 6 % THD (non-linear load)
1kVA
2kVA
3kVA
1kVA
2kVA
3kVA
1kVA
2kVA
3kVA
Sinus EVO 1-3 KVA
0.9
120- 300VAC
40Hz ~ 70 Hz
1PH - N - PE
±1% (Battery Mode)
50 Hz ± 0.5% or 60Hz ± 0.5%
3:1
0
4 ms (typical)
Pure Sinus
3 IEC Type + 1 Schuko
3 IEC Type + 1 Schuko
3 IEC Type + 2 Schuko
EXIST
EXIST
90%
88%
12 V / 9 AH
2 x 7 Ah
4 x 9 Ah
6 x 9 Ah
4 hour 90% capacity (typical)
1.0 A (max.)
EXIST (@ start-up, 1/per week)
Optional, with battery connector
27.4 VDC ± 1%
54.7 VDC ±1%
82.1 VDC ±1%
20