Technical Specifications - LEGRAND DAKER DK Plus Series Installation Manual

1 kva-2 kva-3 kva
Hide thumbs Also See for DAKER DK Plus Series:
Table of Contents

Advertisement

Available languages

Available languages

General characteristics
Nominal power (VA)
Active Power (W)
Technology
Waveform
Bypass
Transfer time AC to DC
Input characteristics
Input Connection
Rated input voltage
Range of input voltage
Rated input frequency
Maximum input current
Total harmonic distortion of
the input current
Input power factor
Number of input phases
Output characteristics
Outlets
Rated output voltage
Rated output frequency
Crest factor
Total harmonic distortion of
the input current
Efficiency
Overload capacity
Number of output phases
Batteries and battery charger characteristics
Number of batteries
Battery type
60
3 101 70
1000
900
on-line, double conversion, VFI-SS-111
internal automatic bypass
external maintenance bypass (optional)
10 A,
IEC 320-C14
from 160 V to 288 V at full load
6,8 A
≥ 0.99 (with full linear load)
(6) 10 A,
IEC 320-C13
adjustable to 200/208/220/230/240 V
< 3% at full linear load
< 7% at full non-linear load
up to 90%
120% for 30 seconds
150% for 10 seconds
3
Lead-acid sealed without maintenance (VRLA)

7 Technical specifications

3 101 71
2000
1800
sinusoidal
0 ms
10 A,
IEC 320-C14
230 V
50 / 60 Hz ± 5 %
13,6 A
THDi < 3%
Single phase
(6) 10 A,
IEC 320-C13
230 V ± 1%
50 / 60 Hz ± 0,1%
3:1
up to 91%
105% continuous
Single phase
6
3 101 72
3000
2700
16 A,
IEC 320-C20
20,0 A
(6) 10A,
IEC 320-C13
+
(1) 16A
IEC 320-C19
up to 92%
6

Hide quick links: