01: Output Voltage Setting
Interface
02: Frequency Converter Enable/Disable
Interface
03: Output Frequency Setting
Interface
04: ECO Enable/Disable
Interface
Setting
Parameter 3: Output voltage
For 208/220/230/240 VAC models, you may choose the following output
voltage:
208: presents output voltage is 208Vac
220: presents output voltage is 220Vac
230: presents output voltage is 230Vac (Default)
240: presents output voltage is 240Vac
For 110/150/120/127 VAC models, you may choose the following output
voltage:
110: presents output voltage is 110Vac
115: presents output voltage is 115Vac
120: presents output voltage is 120Vac (Default)
127: presents output voltage is 127Vac
Setting
Parameter 2 & 3: Enable or disable converter mode. You may choose the
following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable(Default)
Setting
Parameter 2 & 3: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50: presents output frequency is 50Hz
BAT 60: presents output frequency is 60Hz
If converter mode is enabled, you may choose the following output
frequency:
CF 50: presents output frequency is 50Hz
CF 60: presents output frequency is 60Hz
Setting
Parameter 3: Enable or disable ECO function. You may choose the
following two options:
ENA: ECO mode enable
DIS: ECO mode disable (Default)
14