8: Autonomy Limitation Setting
Interface
9: Total Battery Ah
Interface
00: Exit Setting
Setting
Parameter 3: Set up backup time on battery mode for general outlets.
0-999: setting the backup time in minutes from 0-999 for general outlets
on battery mode.
0: When setting as "0", the backup time will be only 10 seconds.
999: When setting as "999", the backup time setting will be disabled.
(Default)
Setting
Parameter 3: Set up total battery AH value of the UPS. (unit: AH)
7-999: setting the total battery capacity from 7 to 999. Please set up this
figure if external battery pack is connected.
If the UPS is standard model, the default setting is 9AH.
If the UPS is long-run model, the default setting is 65AH.
16