2.
Rack Installation Specifications
Rack Installation Requirements
Installing 9 to 10 DEs for Each Node
This section describes the required (estimated) length of cable for configuring 9 or 10 DEs connected to each
node with four CEs installed.
The supplied cable can be used for connecting between the FE and CE#0.
A 3m or longer QSFP cable and a 5m or longer management cable are required between the FE, and the CE#1
and CE#2 in the first expansion rack (or Expansion Rack#0).
A 10m or longer cable is required between the FE and the CE#3 in the second expansion rack (or Expansion
Rack#1).

Table 28 Required Cable Length/Quantity (When Connecting 9 to 10 DEs per Node)

Cable length
Cables that are supplied as standard (1.1m/3m)
Frontend cables (3m/5m)
Frontend cables (10m/10m)
*1: The required quantity varies depending on the number of CEs that are to be connected.
Figure 47 Frontend Cable Connection Example (When Connecting 10 DEs for Each Node in a 19-inch Rack [for GS,
1800mm])
Base rack (rear)
DE
DE
DE
DE
DE
DE
DE
DE
DE
DE
CE#0
FE
PDU#3
PDU#2
PDU#1
PDU#0
QSFP copper cable (supplied as standard)
1.1m
QSFP copper cable (for extensions)
3m
QSFP active optical cable (for extensions)
10m
FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide
Quantity (*1)
One set (supplied as
standard)
Up to two sets
Up to one set
Expansion rack#0
Expansion rack#1
DE
DE
DE
DE
DE
CE#2
DE
DE
DE
DE
DE
DE
CE#3
DE
DE
DE
DE
DE
DE
DE
DE
DE
DE
DE
DE
DE
DE
CE#1
DE
PDU#3
PDU#3
PDU#2
PDU#2
PDU#1
PDU#1
PDU#0
PDU#0
Management cable (supplied as standard)
Management cable (for extensions)
Management cable (for extensions)
70
Copyright 2020 FUJITSU LIMITED
Connection destination
For CE#0
For CE#1 to CE#2
For CE#3
Expansion rack#2
DE
DE
DE
DE
PDU#1
PDU#0
3m
5m
10m
P3AM-9422-13ENZ0