This section explains the requirements for connecting a power distribution unit (vertical type) with the ETERNUS
DX8700 S3/DX8900 S3.
Keep the total current consumption of power cords that connect to outlets OUT1 to OUT8 within 24A for each
power distribution unit when connecting.
Connect to the outlets using the connection order to the power distribution units which is the same as the
installation order in the rack.
When connecting a new enclosure, if the total current consumption of each power distribution unit exceeds
24A, connect to the next power distribution unit.
For details on the current consumption of each power cord for each type of enclosure, refer to
Specifications" (page
For mainframe connections, power distribution units (vertical type) cannot be installed. Power distribution
units (horizontal type) must be selected.
FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide
38).
57
Copyright 2020 FUJITSU LIMITED
"Outlet/Socket
P3AM-9422-13ENZ0