2.
Rack Installation Specifications
Rack Installation Requirements
■
Power Distribution Units (Vertical Type)
This section explains the requirements for connecting a power distribution unit (vertical type) with the ETERNUS
DX8700 S3/DX8900 S3.
Keep the total current consumption of power cords that connect to outlets OUT1 to OUT8 within 24A for each
•
power distribution unit when connecting.
Connect to the outlets using the connection order to the power distribution units which is the same as the
•
installation order in the rack.
When connecting a new enclosure, if the total current consumption of each power distribution unit exceeds
•
24A, connect to the next power distribution unit.
For details on the current consumption of each power cord for each type of enclosure, refer to
Specifications" (page
•
For mainframe connections, power distribution units (vertical type) cannot be installed. Power distribution
units (horizontal type) must be selected.
FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide
38).
57
Copyright 2020 FUJITSU LIMITED
"Outlet/Socket
P3AM-9422-13ENZ0