Rack Installation Specifications; Rack Installation Requirements; Placement In The Rack - Fujitsu ETERNUS DX8100 S3 Site Planning Manual

Hybrid
Hide thumbs Also See for ETERNUS DX8100 S3:
Table of Contents

Advertisement

2.

Rack Installation Specifications

This chapter provides the rack installation specification of the ETERNUS DX.

Rack Installation Requirements

This section explains the requirements for installing the ETERNUS DX in a 19-inch rack.

Placement in the Rack

The center of gravity must be taken into consideration to prevent a rack from toppling over when installing in a
rack. Enclosures should generally be installed from bottom to top to lower the center of gravity and to ensure
the safe use of racks.
When determining the rack-mounting layout of each enclosure and power distribution unit, consider the
length of each cable. For example, if the ETERNUS DX is installed at the top of a 2000mm rack and a 4m
power cord is used, the surplus length of the power cord at the bottom of a rack should be about 2m.
If the storage system is installed at the bottom of a rack, a space for the surplus of cables may not be avail-
able in some racks, preventing the storage system from being pulled out when maintenance work is re-
quired.
In this case, secure a space of 1U or more at the bottom when installing the storage system.
For 19-inch racks, install the power distribution unit (horizontal type) in the lower part of the rack.
For 19-inch racks (with standard door, 2000mm) and 19-inch racks (with a DX8000 series dedicated door,
2000mm), install the power distribution unit (vertical type) in the dedicated spaces at the sides of the rack.
When connecting seven or more drive enclosures to a single controller enclosure, select the power distribu-
tion units (vertical type).
Note that power distribution units (vertical type) cannot be used for mainframe connections. Power distri-
bution units (horizontal type) must be selected.
Installation Example (ETERNUS DX8100 S3)
The following figures show examples of when the ETERNUS DX8100 S3 is installed in a 19-inch rack.
The power control device SCCI/PPC is provided with a 2m cable.
Install the SCCI/PPC and the controller enclosure in a location within reach of the cable.
Installing controller enclosures, drive enclosures, the SCCI/PPC, and the power distribution unit in the same
rack is recommended.
FUJITSU Storage ETERNUS DX8100 S3/DX8700 S3/DX8900 S3 Hybrid Storage Systems Site Planning Guide
48
Copyright 2020 FUJITSU LIMITED
P3AM-9422-13ENZ0