Use the AZL2... or ACS410 to always set the exact value of the required time (multiples of increments of 0.147 seconds, 0.294 seconds or 4.851 seconds).
When parameterizing minimum or maximum times, the possibility of a ±7% tolerance must be taken into consideration.
For minimum values: The value to be parameterized must be at least 7% greater. For maximum values: The value to be parameterized must be at least 7% smaller.
Example:
Special case here:
Calculation:
Value to be parameterized (parameter 266): Must be equal to or greater than the calculated value (e.g. 29.106 seconds)
Example:
Calculation:
Value to be parameterized (parameter 267): Must be equal to or smaller than the calculated value (e.g. 4.557 seconds)
Legend
TSA
Safety time
tw
Waiting time
t1
Prepurge time
t3
Preignition time
1)
Repetition (maximum number of startups per controlled start)
16/61
Building Technologies
Prepurge time shall be set to 30 seconds
The preignition time is made up of parameter 266 and a time of 5.6 seconds that cannot be parameterized.
Burner controls for the supervision of 1- or 2-stage gas or gas / oil burners of