Error Code List - Siemens LMO39 Series Basic Documentation

Burner controls
Table of Contents

Advertisement

Error code
Clear-text
Loc:
2
No flame at the end of safety time
Loc:
3
Free
Loc:
4
Extraneous light
Loc:
5
Free
Loc:
7
Loss of flame
Loc:
8
Oil preheater
Loc:
9
Free
Loc:
10
Errors that cannot be assigned (application)
Internal error
Building Technologies

20 Error code list

Table 10: Error code list
Basic Documentation LMO39...
20 Error code list
Potential cause
No establishment of flame at the end of safety time
- Defective or soiled fuel valves
- Defective or soiled flame detector
- Poor adjustment of burner, no fuel
- Defective ignition equipment
Free
Extraneous light on burner startup
Free
Loss of flame during operation too frequent
(limitation of repetitions)
- Defective or soiled fuel valves
- Defective or soiled flame detector
- Poor adjustment of burner
Time supervision oil preheater
Oil preheater failed 5 times during prepurging
Free
Wiring error or internal error, output contacts, other
errors, manual locking
55/61