5.2 Installation

007002_k_en_--
Observe the country-specific regulations for the exact installation height!
Manual call points FDM223 and FDM224 (housing FDMH293-x or
FDMH297-R)
w
The manual call point FDM223/FDM224 is prepared for installation. See the
chapter 'Preparing the housing'.
1. Secure the housing at a height of 0.9...1.6 m on an even surface.
If you are using housing FDMH293-x: In wet areas, only use the screw
holes marked by arrows (see diagram below).
Housing FDMH297-R may not be used in wet areas.
2. Pull the cables through the entry opening(s) into the housing.
Cable entry from the rear of the housing is only permitted for housing
FDMH297-R.
In wet areas, use metal cable glands M20 x 1.5 (accessories).
a The manual call point FDM223/FDM224 is now prepared for electrical
connection.
Figure 9: Screw holes in housing FDMH293-x
Figure 10: Housing FDMH297-R with breakout points for cable entries and screws (cable entries and
screw holes are compatible with old housings)
Mounting / Installation
Installation
29 | 54