Status Query; Performance Check - Siemens FDM223 Technical Manual

Manual call point
Hide thumbs Also See for FDM223:
Table of Contents

Advertisement

Maintenance / Repair
7

Status query

7.2 Status query

7.3 Performance check

44 | 54
Status query on the detector exchanger and tester
Each manual call point for FDnet/C-NET features a proximity interface (MC link).
Using this interface, it is possible to read out data from the device in a proximity
method over short distances with the detector exchanger and tester FDUD292 or
the intelligent detector tester FDUD293.
To ensure correct communication between the testing device and the manual call
point, the alarm indicator on the manual call point must be aligned with a sensor on
the testing device. For this purpose, turn the testing device 45 degrees and push it
down by approx. 1 cm.
You will find more information in documents 007227 and 009718.
Status query on the control panel
Depending on the authorization level of the user and the control panel type,
different actions can be performed from the control panel.
Observe the notices in the control panel documentation.
Document 009052 applies to fire control panels FC20xx.
Document A6V10333448 applies to fire control panels FC72x.
The devices are automatically subjected to a performance check during the self-
test. Nevertheless, it is necessary to check the devices on site at regular intervals.
Recommendation:
Check the devices every year.
Replace heavily soiled or damaged devices.
No other special maintenance work is necessary.
You will find more detailed information in the fire detection system documentation.
See also
2
Checking function [➙ 39]
007002_k_en_--

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fdm224Fdm223hFdm224h

Table of Contents