8.1 Technical data

Detector line
Line separator
The line separator is closed via an actuation signal from the control panel. Required line voltage: DC 12...33 V
(normal range)
External alarm indicators Number of external alarm indicators
007002_k_en_--

8 Specifications

You will find information on approvals, CE marking, and the relevant EU directives
for this device (these devices) in the following document(s); see 'Applicable
documents' chapter:
Document 007001
Document 008345
Operating voltage
Operating current (quiescent)
Maximum current connection factor
Quiescent current connection factor
Address connection factor
Separator connector factor
Protocol
System compatibility
Line voltage:
Nominal
Minimum
Maximum
Voltage at which the line separator
opens:
Minimum
Maximum
Permanent current when switches are
closed
Switching current (e.g., in the event of
a short-circuit)
Leakage current when switches are
open
Serial impedance when switches are
closed
that can be connected
Voltage
Current
Length of line
Specifications
Technical data
DC 12...33 V
200 μA
1
1
1
1
FDnet/C-NET
See 'List of compatibility'
DC 32 V (= V
)
nom
DC 12 V (= V
)
min
DC 33 V (= V
)
max
DC 7,5 V (= V
)
SO min
DC 10.5 V (= V
)
SO max
Max. 1.5 A (= I
)
C max
Max. 2 A (= I
)
S max
Max. 1 mA (= I
)
L max
Max. 0.4 Ω (= Z
)
C max
2
DC 10...17 V
9...15 mA
Max. 30 m with unshielded cables, or
when the shielding is connected to the
positive pole of the detector base
Max. 5 m, if the shielding is connected
to earth
8
47 | 54