ABB Relion 650 Series Operation Manual page 87

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 500 096-UUS B
Check the actual state of the connected binary inputs.
Measure output contacts using the voltage drop method of applying at least the minimum
contact load given for the output relays in the technical data, for example 100 mA at 24 V
AC/DC.
A
GUID-BBAEAF55-8D01-4711-A71D-BBC76B60BA3D V1 EN-US
Figure 52: Testing output contacts using the voltage drop method
1
2 Contact voltage drop
3 Load
4 Supply voltage
650 series
Operation manual
Change the parameter
3PhaseAnalogGroup/SMAI_20_n:1 (n= the number of the SMAI used).
Changing the
skills.
Change the parameter in PCM600, see PCM600 documentation.
In LHMI, select Main menu/Tests/I/O modules. Then navigate to the board with the
actual binary input to be checked.
Check the actual state of the connected binary inputs through PCM600, see PCM600
documentation.
Output relays, especially power output relays, are designed for breaking high
currents. Due to this, layers of high resistance may appear on the surface of
the contacts. Do not determine proper functionality of connectivity or contact
resistance by measuring with a regular hand-held ohm meter.
V
1
4
Contact current
© Copyright 2013 ABB. All rights reserved
Negation in Configuration/Analog modules/
Negation parameter is not recommended without special
2
3
Section 8
Troubleshooting
81

Advertisement

Table of Contents
loading

Table of Contents