1MRK 500 096-UUS B
closed and unavailable if the configuration of the 650 series does not contain a communication
line of the protocol. If a protocol is configured, the corresponding IP port is open all the time.
There are some restrictions and dependencies:
The IP port used for DHCP (default UDP port 67) between the IED and a computer is fixed and
cannot be changed.
The IP port used for IEC 61850 (default TCP port 102) is fixed and cannot be changed.
The IP ports used for DNP3 are configurable. The communication protocol DNP3 could
operate on UDP (default port 20 000) or TCP (default port 20 000). It is defined in the
configuration which type of Ethernet communication is used. Only one type is possible at a
time.
The IP port used for FTP (default TCP port 21) can be changed in the IED if needed by a 3rd
party FTP client.
PCM600 uses IED configuration protocol (TCP port 2102) and FTP ports to communicate with the
IED. The port used by the IED configuration protocol is fixed and cannot be changed. FTP port is
used for uploading disturbance records (DR).
For Field service tool, the IP port for a proprietary SPA protocol is used (TCP port 7001) and the
port is fixed and cannot be changed.
IP routing is not possible via any of the physical interfaces.
Some IP ports are not possible to use in all physical interfaces.
ANSI12000172 V1 EN-US
Figure 11:
650 series
Operation manual
See the 650 series technical manual and the corresponding protocol
documentation on how to configure a certain communication protocol for the 650
series.
If the FTP port is changed PCM600 cannot be used since it is not possible to
configure it to use other IP-ports than port 21 for FTP.
Ethernet port used for PCM600 only, front view