1MRK 500 096-UUS B
Table 19:
Access rights explanation
Access rights
Config – Basic
Config – Advanced
FileTransfer – Tools
UserAdministration
Setting – Basic
Setting – Advanced
Control – Basic
Control – Advanced
IEDCmd – Basic
IEDCmd – Advanced
FileTransfer – Limited
DB Access normal
Audit log read
Setting – Change Setting Group
Security Advanced
IED users can be created, deleted and edited only with the IED Users tool within PCM600. Logging
on or off can only be done on the local HMI on the IED, there are no users, roles or rights that can
be defined on local HMI.
At delivery, the IED has a default user defined with full access rights. PCM600 uses this default
user to access the IED. This user is automatically removed in IED when users are defined via the
IED Users tool in PCM600.
Default User ID: Administrator
Password: Administrator
650 series
Operation manual
Explanation
Configuration – Basic is intended for engineers that only adapt an existing configuration e.g.
the I/O-Configuration using SMT
Configuration – Advanced is intended for engineers that do the whole application engineering
and using e.g. ACT
FileTransfer – Tools is used for some configuration files for the configuration and shall have the
same value as Config – Advanced
UserAdministration is used to handle user management e.g. adding new user
Setting – Basic is used for basic settings e.g. control settings and limit supervision
Setting – Advanced is used for the relay engineer to set settings e.g. for the protection
functions
Control – Basic is used for a normal operator without possibility to bypass safety functions e.g.
interlock or synchro-check bypass
Control – Advanced is used for an operator that is trusted to do process commands that can be
dangerous
IEDCmd – Basic is used for commands to the IED that are not critical e.g. Clear LEDs, manual
triggering of disturbances
IEDCmd – Advanced is used for commands to the IED that can hide information e.g. Clear
disturbance record
FileTransfer - Limited is used for access to disturbance files e.g. through FTP
Database access for normal user. This is needed for all users that access data from PCM
Audit log read allows reading the audit log from the IED
Setting – Change Setting Group is separated to be able to include the possibility to change the
setting group without changing any other setting
Security Advanced is the privilege required to do some of the more advanced security-related
settings
Only characters A - Z, a - z and 0 - 9 shall be used in user names. User names are not
case sensitive. For passwords see the Password policies in PCM600.
First user created must be appointed the role SECADM to be able to write users,
created in PCM600, to the IED.