Replacement Of Tank - SMC Networks HRS012-A-10 Series Service Manual

Thermo-chiller
Hide thumbs Also See for HRS012-A-10 Series:
Table of Contents

Advertisement

HRX-MM-N007
Chapter 4
Service Procedure

4.5.11 Replacement of tank

<HRS-A/W->
Be sure to shut off the breaker of the facility power supply (the user's
machine power supply) before replacement work.
 Removal
1.
Discharge the circulating fluid referring the 4.2.2 Discharge of the circulating fluid and
facility water.
2.
Remove the upper panel, the panels on both sides and the front panel referring the 4.2.1
Removal and the mounting of the panel.
3.
Remove the hose clamp and remove hose A and hose B.
4.
Remove the level switch pin [LS1] (two red lines) from the main board.
5.
Remove the tank.
Grommet
3.
Hose B
4.5 Replacement Procedure
4-38
Table 4-18 Part number of service parts (Tank)
Description
Tank
[Tips]
Use "57031-6000" of MOLEX for removing.
Our part no.:HRS-S0056
4.
Remove
Main board
the pin
3.
Hose A
Fig. 4.5-22 Removal of tank
Part number
HRS-S0025
Tank lid
5.
Tank
Hose clamp
HRS Series

Hide quick links: