SMC Networks HRS012-A-10 Series Service Manual page 149

Thermo-chiller
Hide thumbs Also See for HRS012-A-10 Series:
Table of Contents

Advertisement

 Mounting
1.
Apply the liquid gasket to the threads of the temperature sensor and mount the temperature
sensor using a spanner/wrench.
2.
Put through the electric wire from the grommet to the inside of the electric equipment.
3.
Mount the connector (PT1) of the temperature sensor.
4.
Mount the upper panel and the rigrt panel in reversed order of removal. (Fixing screws ×8)
HRS Series
[Tips]
Do not apply the liquid gasket to the first thread. Otherwise, the liquid gasket
will spread to the circulating circuit and cause the product to fail. To prevent
dust from getting caught in the threads, check there is no dust stuck to the
threads before the screw is mounted.
HRX-MM-N007
Chapter 4
Service Procedure
4.5 Replacement Procedure
4-13