Digital outputs

Number
Switchable voltages / currents
Operating frequency
Electrical isolation between
groups
Permitted length of connecting
cable
Current / loading
– no current
– 0,2 A
– 1 A
– 2 A
Status display with LED
Insulation resistance against in-
ternal system voltage
– Relay outputs
Festo KBS_FEC FC20- 0206NH English
8 relay outputs (potential-free)
5A / 250 V AC, 5A / 30 V DC; mini-
mum load: 10 mA at 5 V DC
max. 25 Hz
yes, one group with 4 relays,
two groups each with 2 relays
max. 30 m
Ohm
resistive load
20 Mio. cycles
1 Mio cycles
500.000 cycles 300.000 cycles
300.000 cycles 100.000 cycles
yes
mains voltages from overvoltage
category II can be switched; rated
voltage of insulation: 300 V AC
inductive load
20 Mio. cycles
800.000 cycles