SUN2000-(33KTL, 40KTL)-JP
User Manual
Figure 7-6 Quick Settings screen (logging in as an advanced user)
Issue 07 (2019-06-30)
Set the power grid code that applies to the country or region where the power station is located and
the inverter model.
Set user parameters based on the current date and time.
Set Baud rate, RS485 protocol, and Address based on site requirements. Baud rate can be set to
4800, 9600, or 19200. RS485 protocol can be set to MODBUS RTU, and Address can be set to any
value in the range of 1 to 247.
When multiple inverters communicate with the SmartLogger over RS485, the addresses for all the
inverters on each RS485 route must be within the address range set on the SmartLogger and cannot
be duplicate. Otherwise, the communication will fail. In addition, the baud rates of all the inverters
on each RS485 route must be consistent with the SmartLogger baud rate.
Copyright © Huawei Technologies Co., Ltd.
7 System Commissioning
97