The request specifies the starting address and the number of registers to read. If a function
spans multiple registers, the first register contains the high order value.
Note that PLC Addressing (Base 1) is used.
Dec
Hex
Function
1 0x0001
Model ID
2 0x0002
Language
3 0x0003
Current Flow
Rate
4 0x0004
Flow Percentage
5 0x0005
Analog Input 1
6 0x0006
Analog Input 2
7 0x0007
Analog Output
8 0x0008,
Totalizer User
0x0009
Strokes
10 0x000A,
Totalizer User
0x000B,
Volume
0x000C,
0x000D
14 0x000E,
Totalizer User
0x000F
Hours
16 0x0010
Totalizer User
Power Cycles
17 0x0011,
Totalizer Unit
0x0012
Strokes
19 0x0013,
Totalizer Unit
0x0014,
Volume
0x0015,
0x0016
23 0x0017
Totalizer Unit
Hours
25 0x0019
Totalizer Unit
Power Cycles
26 0x001A
Calibrated
Volume
MODBUS SOFTWARE DEFINITION
Description
Read the Model ID as an enumeration associated with the
maximum flow rate of the pump:
Output Code 2 - 5.6 GPH (21.2 l/h) 175 psi (12.0 bar)
Output Code 3 - 14.0 GPH (53.0 l/h) 75 psi (5.0 bar)
Output Code 4 - 18.0 GPH (68.1 l/h) 50 psi (3.5 bar)
Read the Language Setting as an enumeration:
1=English
2=French
3=Portuguese
4=Spanish
5=Chinese)
Read the Current Flow Rate as an integer representing XX.XX
GPH/LPH. The range is 0000-9999.
Read the Flow Percentage as an integer representing
XXX.XX%. The range is 00000-10000.
Read Analog Input 1 as an integer representing XX.X mA. The
range is 000-200.
Read Analog Input 2 an integer representing XX.X mA. The
range is 000-200.
Read Analog Output an integer representing XX.X mA. The
range is 000-200.
Read Totalizer User Strokes as an integer. This is stored in two
registers.
Read Totalizer User Volume as an integer representing Gal or L
depending on current unit setting. This is stored in four
registers.
Read Totalizer User Hours an integer representing the number
of hours the motor has been operated. This uses two registers.
Read Totalizer User Power Cycles as an integer.
Read Totalizer Unit Strokes as an integer. This is stored in two
registers.
Read Totalizer Unit Volume as an integer representing Gal or L
depending on current unit setting. This is stored in four
registers.
Read Totalizer Unit Hours an integer representing the number
of hours the motor has been operated. This uses two registers.
Read Totalizer Unit Power Cycles as an integer.
Read the Calibrated Volume as an integer representing XX.XX
mL. This volume of a single stroke based on the calibration.