Causes of malfunction
Fault clearance
24 hour service hotline
Checking the switching signal
VEGASWING 51 - - contactless electronic switch
7 Maintenance and fault rectification
7.1 Maintenance
When used as directed in normal operation, VEGASWING 51
is completely maintenance free.
7.2 Remove interferences
VEGASWING 51 offers maximum reliability. Nevertheless,
faults can occur during operation. These may be caused by the
following, e.g.:
Sensor
l
Process
l
Supply
l
Signal processing
l
The first measure to be taken is to check the output signal. In
many cases, the causes can be determined this way and the
faults rectified.
However, should this measures not be successful, call the
VEGA service hotline in urgent cases under the phone no. +49
1805 858550.
The hotline is available to you 7 days a week round-the-clock.
Since we offer this service world-wide, the support is only
available in the English language. The service is free of
charge, only the standard telephone costs will be charged.
?
Control lamps off
l
Voltage supply interrupted.
à
Check the voltage supply and the cable connection
à
Exchange the electronics module
?
Signal lamp flashes red
l
There was no load connected when connecting to
power supply
à
Connect the instrument correctly
à
Check if the tuning fork is damage or extremely
corroded
l
Frequency error
à
Adjust the instrument correctly
Maintenance and fault rectification