Contactless electronic switch
VEGASWING 51 - - contactless electronic switch
1
2
Fig. 9: Connection, valve plug DIN 43650 with IDC method of termination
1
Compression nut
2
Cable
3
Split taper socket
4
Seal insert
5
Strand
6
Plug housing
The instrument is used for direct control of relays, contactors,
magnet valves, warning lights, horns etc. It must not be
operated without intermediately connected load, because the
electronic would be destroyed if connected directly to mains. It
is not suitable for connection to low voltage PLC inputs.
Domestic current is temporarily lowered below 1 mA after
switching off the load so that contactors, whose holding current
is lower than the constant domestic current of the electronics
(3 mA), are reliably switched off.
Connecting to voltage supply
4
3
19