Appendix B. Vendor Information - Riello; Appendix B.1. 905 Modbus Rtu Mappings To Bacnet, Metasys N2 And Lonworks - SMC Sierra Monitor FieldServer ProtoNode FPC-N38 Startup Manual

For interfacing riello array boilers: 905, to building automation systems: bacnet ms/tp, bacnet/ip, modbus tcp/ip, metasys n2 and lonworks
Hide thumbs Also See for FieldServer ProtoNode FPC-N38:
Table of Contents

Advertisement

Appendix B. Vendor Information - Riello

NOTE: All Modbus TCP/IP registers are the same as the Modbus RTU registers for the serial device. If
this point list is needed, contact the OEM. The Modbus TCP/IP node address of the device is also
the same as the Modbus RTU node address.

Appendix B.1. 905 Modbus RTU Mappings to BACnet, Metasys N2 and LonWorks

Point Name
Reset Curve Boiler Design
Reset Curve Boiler Mild Weather
Reset Curve Outdoor Mild Weather
Reset Curve Outdoor Design
Warm Weather Shutdown
Reset Curve Boiler Maximum
Reset Curve Boiler Minimum
Night Setback
Power Level For Entire System
Cascade Ch Mode X SP
System Supply SP
System Supply Sensor Temp
Outdoor Sensor Temp
Cascade Pump Status
Boiler 1 Available / Present
Boiler 2 Available / Present
Boiler 3 Available / Present
Boiler 4 Available / Present
Boiler 5 Available / Present
Boiler 6 Available / Present
Boiler 7 Available / Present
Boiler 8 Available / Present
Boiler 1 Is Active / Heating
Boiler 2 Is Active / Heating
Boiler 3 Is Active / Heating
Boiler 4 Is Active / Heating
Boiler 5 Is Active / Heating
Boiler 6 Is Active / Heating
Boiler 7 Is Active / Heating
Boiler 8 Is Active / Heating
Boiler 1 Has Error
Boiler 2 Has Error
Boiler 3 Has Error
Boiler 4 Has Error
Boiler 5 Has Error
Boiler 6 Has Error
Boiler 7 Has Error
Boiler 8 Has Error
Boiler 1 Requires Service
Boiler 2 Requires Service
Boiler 3 Requires Service
Boiler 4 Requires Service
Boiler 5 Requires Service
Boiler 6 Requires Service
Boiler 7 Requires Service
Boiler 8 Requires Service
Boiler Address
Power Level For The Boiler
Boiler Supply SP
Heat Demand Type
System Sensor Temp
Dhw Temp
BACnet
N2
BACnet
Object
Data
Object Type
ID
Type
AO
AV
1
AV
2
AO
AO
AV
3
AO
AV
4
AO
AV
5
AO
AV
6
AO
AV
7
AV
8
AO
AI
AI
9
AO
AV
10
AI
11
AI
AI
AI
12
AI
AI
13
BI
14
DI
DI
BI
15
DI
BI
16
BI
17
DI
DI
BI
18
DI
BI
19
BI
20
DI
DI
BI
21
DI
BI
22
BI
23
DI
DI
BI
24
DI
BI
25
BI
26
DI
DI
BI
27
DI
BI
28
DI
BI
29
DI
BI
30
DI
BI
31
BI
32
DI
DI
BI
33
BI
34
DI
DI
BI
35
DI
BI
36
DI
BI
37
BI
38
DI
DI
BI
39
BI
40
DI
DI
BI
41
DI
BI
42
BI
43
DI
DI
BI
44
DI
BI
45
BI
46
DI
AO
AV
47
AI
AI
48
AI
49
AI
AI
AI
50
AI
AI
51
AI
52
AI
Page 36 of 43
Riello ProtoNode Start-up Guide
N2
Address
LonWorks Name
1
nvi/nvoResCvBlDs_XXX
2
nvi/nvoResCvBMWt_XXX
3
nvi/nvoResCvOMWt_XXX
4
nvi/nvoResCvOtDs_XXX
5
nvi/nvoWmWthShDn_XXX
6
nvi/nvoResCvBlMx_XXX
7
nvi/nvoResCvBlMn_XXX
8
nvi/nvoNtStbk_XXX
9
nvoPwrLvl_XXX
10
nvi/nvoCscChMdSP_XXX
11
nvoSysSupSP_XXX
12
nvoSysSpSnTp_XXX
13
nvoOutSenTmp_XXX
14
nvoCscPmpSt_XXX
15
nvoB1Avail_XXX
16
nvoB2Avail_XXX
17
nvoB3Avail_XXX
18
nvoB4Avail_XXX
19
nvoB5Avail_XXX
20
nvoB6Avail_XXX
21
nvoB7Avail_XXX
22
nvoB8Avail_XXX
23
nvoB1ActHt_XXX
24
nvoB2ActHt_XXX
25
nvoB3ActHt_XXX
26
nvoB4ActHt_XXX
27
nvoB5ActHt_XXX
28
nvoB6ActHt_XXX
29
nvoB7ActHt_XXX
30
nvoB8ActHt_XXX
31
nvoB1Err_XXX
32
nvoB2Err_XXX
33
nvoB3Err_XXX
34
nvoB4Err_XXX
35
nvoB5Err_XXX
36
nvoB6Err_XXX
37
nvoB7Err_XXX
38
nvoB8Err_XXX
39
nvoB1ReqSvc_XXX
40
nvoB2ReqSvc_XXX
41
nvoB3ReqSvc_XXX
42
nvoB4ReqSvc_XXX
43
nvoB5ReqSvc_XXX
44
nvoB6ReqSvc_XXX
45
nvoB7ReqSvc_XXX
46
nvoB8ReqSvc_XXX
47
nvi/nvoBlrAddr_XXX
48
nvoBlrPwrLvl_XXX
49
nvoBlrSupSP_XXX
50
nvoHtDemTyp_XXX
51
nvoSysSenTmp_XXX
52
nvoDhwTemp_XXX
LonWorks SNVT
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_lev_percent
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_temp_p
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_switch
SNVT_count_f
SNVT_lev_percent
SNVT_temp_p
SNVT_count_f
SNVT_temp_p
SNVT_temp_p