Bacnet/Ip Or Modbus Tcp/Ip: Change The Protonode Ip Address; Connect The Pc To Protonode Via The Ethernet Port - SMC Sierra Monitor FieldServer ProtoNode FPC-N38 Startup Manual

For interfacing riello array boilers: 905, to building automation systems: bacnet ms/tp, bacnet/ip, modbus tcp/ip, metasys n2 and lonworks
Hide thumbs Also See for FieldServer ProtoNode FPC-N38:
Table of Contents

Advertisement

5

BACNET/IP OR MODBUS TCP/IP: CHANGE THE PROTONODE IP ADDRESS

5.1

Connect the PC to ProtoNode via the Ethernet Port

Connect a CAT5 Ethernet cable (Straight through or Cross-Over) between the local PC and
ProtoNode.
The Default IP Address of ProtoNode is 192.168.1.24, Subnet Mask is 255.255.255.0. If the PC
and ProtoNode are on different IP Networks, assign a static IP Address to the PC on the
192.168.1.xxx network.
For Windows XP:
Go to
Right-click on Local Area Connection > Properties
Highlight
For Windows 7 or later:
Go to
>
Right-click on Local Area Connection > Properties
Highlight
For Windows XP and Windows 7, use the following IP Address:
Click
>
>
>
>
>
twice.
Page 19 of 43
Riello ProtoNode Start-up Guide
>
>

Hide quick links:

Advertisement