Installation (for qualified installers only)
Clearances
Due to the high temperature of the heater, it should be located out of traffic and away from furniture and
draperies.
Side
k
Wall
l
Mantel Clearances
The maximum mantel depth is 12" (305mm).
NOTE: The combustible area above the facing must not protrude more than 3/4" (20mm) from the facing.
If it does, it is considered a mantel and must meet the mantel requirements listed in this manual.
Mantel Height
Above Base of Insert (n)
© Travis Industries
n
m
p
x
37"+(940mm+)
36"(915mm)
35"(889mm)
34"(864mm)
33"(839mm)
32"(813mm)
31"(788mm)
9/17/2020 - 1536
k Sidewall to Insert
l Side Facing
(non-combustible)
m Top Facing*
(non-combustible)
n Mantel* (combustible or
non-combustible)
p Hearth Extension to the
front
x Extension onto Hearth
1-Piece Panel w/o Trim
1-Piece Panel w/ Trim kit
* Measured from the base of the insert.
NOTE: the non-combustible top facing must
extend 35-1/2" (902mm) above the base of the
insert or to the bottom of the mantel (whichever is
less).
Maximum Mantel Depth
Minimum
Clearances
4" (102mm)
4" (102mm)
35-1/2" (902mm)
35-1/2" (902mm)
0" (0mm)
0" (0mm)
1-1/4" (32mm)
DVL EG GSR2