1.1.3.1.5
Extra Device
Description:
The panel has identified a device at an address that is not in the panel programming.
NOTES:
Only one extra device per loop is ever displayed. Fixing one extra device may display a new
extra device fault (if present)
Extra Device Faults take a longer time to appear and clear than other faults.
Possible causes:
Device not added to the program
Device addressed incorrectly
Device not programmed at all (IDNet address 255, MAPNet address 0)
Suggested solutions:
Check and fix "NO ANSWER" Device
faults as this may clear extra device
Scroll through the Historical
Fault Log for the following
message
"MAPNET EXTRA DEVICE"
Scroll to the NEXT event.
Channel = Loop Number
DEVICE = Address
1< Device > 255
Check Program has a
device at that address
faults
Device = 255 or 0
The device has
not been
addressed.