Delta Modulon Series User Manual page 17

Three phase 15-105 kva 208vac external battery cabinet
Table of Contents

Advertisement

Table 2: specifications of the cables
Battery
Cabinet
9Ah
Capacity
Battery
Module
4
Q'ty
Rated
42A
current
6 AWG
Recom-
(13
mended
mm
2
)
cable
size
x 1 PC
RNB
Terminal
1
14-10
Type*
WARNING:
1. The maximum recommended length of the battery cables is 33 ft (10 m). If
a longer distance is required, you must use larger cables according to the
distance.
2. The battery cabinet is scalable. Therefore, it is highly recommended to use
the full-size (maximum rating according to the full battery capacity) cables
between the UPS and the battery cabinet irrespective of the UPS rating. This
is to ensure safety of the battery input at all times.
DPH-LV-B
18Ah
27Ah
8
12
83A
124A
2/ 0
2 AWG
AWG
(33
(67
mm
2
)
mm
2
)
x 1 PC
x 1 PC
RNBS
RNB
38-10
70-10
36Ah
45Ah
16
20
165A
206A
4/ 0
1/ 0
AWG
AWG
(107
(53
mm
2
)
mm
2
)
x 1 PC
x 2 PCS
RNB
RNB
100-10
60-10
16
54Ah
63Ah
24
28
248A
289A
2/ 0
3/ 0
AWG
AWG
(67
(85
mm
2
)
mm
2
)
x 2 PCS
x 2 PCS
RNB
RNB
70-10
80-10
72Ah
32
330A
4/ 0
AWG
(107
mm
2
)
x 2 PCS
RNB
100-10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dph seriesDph-lv-bDph-60k-lvDph-105k-lv

Table of Contents