Section 4
Setting up a project
4.5.2
52
When using the front port, DHCP server functionality must be activated in the
computer network adapter settings to get the IP address from the relay. Alternatively,
the computer network adapter IP address can be set manually to the same subnet range
as the front port.
GUID-6B209BB8-F07E-4414-B404-EA33CEB71DB2 V1 EN
Figure 33:
Communication port options
Check that the settings are correct to ensure successful configuration access to the
relay.
Computer port settings must match relay settings (IP address, subnet mask,
DHCP).
Any firewall in the computer or in the network must pass required
communication services.
When using the front port and switching the connection from the computer
to another relay, it takes some time before the computer refreshes the relay's
MAC address for front port IP address automatically. The MAC address
can also be reset manually by clearing the computer ARP table.

Importing a 611 series protection relay in a COM600S project

1.
Create a PCM600 project including several IEDs.
1MRS241255 B
611 series
Engineering Manual