ABB Relion 611 Series Engineering Manual page 25

Hide thumbs Also See for Relion 611 Series:
Table of Contents

Advertisement

1MRS241255 B
611 series
Engineering Manual
recommended to divide one big project into multiple smaller
PCM600 projects.
To add a protection relay to a project, a suitable Connectivity package is needed.
Protection relays can be added either while connected or disconnected or through
other means such as an IED template.
IED objects are uniquely named within the PCM600 project.
Parameter setting and configuration in the Parameter Setting tool
Configuration parameters such as CT and VT conversion values of the
transformer module are checked by the tool.
If needed, the setting values are checked and adjusted with the Parameter Setting
tool.
LHMI engineering
The LEDs are configured with Application Configuration.
The LED behavior is defined with Parameter Setting.
The HMI Event Filtering tool can be used to configure event visibility on the
LHMI event list.
Communication protocol engineering
The communication engineering details are protocol-dependent.
The connectivity package creates the IEC 61850 configuration for vertical
communication automatically and it is directly suitable, in most cases, for IEC
61850 client configuration. Either IEC 61850 Configuration tool or IET600 is
needed for configuring horizontal and vertical communication.
The Communication Management tool is used for other protocols; for example
Modbus.
The protection relay restarts automatically when writing a relay
configuration where changes have been made. It is not possible to
communicate with the protection relay during restart.
Relay engineering process
Section 2
17