Com600S Project; Selecting Communication Port For Configuration - ABB Relion 611 Series Engineering Manual

Hide thumbs Also See for Relion 611 Series:
Table of Contents

Advertisement

1MRS241255 B
4.5
4.5.1
611 series
Engineering Manual
GUID-515B4125-7B57-472D-9F18-7744DD0DB483 V1 EN
Figure 32:
Alternative 2: Setting the IP address in IED's Object Properties dialog
box
Choosing between the two ways depends on when the IP address is set. Typing the IP
address via the IED's Object Properties dialog box is possible at any time while
entering it via the configuration wizard can only be done when adding the IED object.
1.
In the Plant Structure view, select the IED to which the IP address is to be
entered.
2.
On the View menu, select Object Properties.
Object Properties dialog box is opened.
3.
Type in the IP address to the IP Address row.

COM600S project

The 611 series connectivity package supports SAB600. A 611 series protection relay
is imported as a 611 series device. It is also possible to import a full PCM600 project
including several 611 series devices to SAB600. In this case, PCM600 project
information is imported to SAB600 using a SCD file.
The 611 series device supports several functions in COM600S.
Controlling the switchgear
Monitoring the measured values
Reading disturbance recordings
Setting parameters

Selecting communication port for configuration

When a relay is configured to a PCM600 project, the connection between the relay and
the tool can be established using a point-to-point link between the relay front port and
the computer or by connecting the computer to the relay rear port over an Ethernet
station bus. In PCM600, the front or rear communication port can be selected from the
project structure.
Section 4
Setting up a project
51