Exporting Scl Files From Pcm600; Exporting Scd Files - ABB Relion 611 Series Engineering Manual

Hide thumbs Also See for Relion 611 Series:
Table of Contents

Advertisement

1MRS241255 B
7.3.1
7.3.1.1
611 series
Engineering Manual
When exporting an SCL file from PCM600, the tool builds a default substation
structure and creates default data sets and control blocks for vertical communication
between the substation client and IEDs. For more information, see the IEC 61850
standards.
In the following example, it is assumed that PCM600 and IET600 are used as the
system configuration tools. Another option is to use the IEC 61850 Configuration tool
inside PCM600. In that case the SCL file export and import operations (steps 1 and 3)
are not needed.
1.
SCL files are exported from PCM600. In this case, a SCD file. It is also possible
to export other SCL file types.
2.
Horizontal and vertical communication is configured using the station
configuration tool, for example, IEC 61850 Configuration tool or IET600.
3.
SCL files are imported to a PCM600 project. In this case, it is the updated SCD
file.
IET 600 (2)
create project
import SCD file
SCD file
configure d ata sets
configure Report CBs
configure GOOSE CBs
export SCD file
PCM 600 (1)
do IED engineering
export SCD file
GUID-5096E041-8757-49F2-BB8D-D02B6222C359 V1 EN
Figure 52:
IEC 61850: signal engineering procedure flow when a complete
station is exported as a SCD file

Exporting SCL files from PCM600

A pre-condition for exporting SCL files from PCM600 is that all IEDs in the project
must be engineered in PCM600. The IEDs require unique name and IP addresses and
they must be set according to the project definitions. IED configurations must be
finalized as far as possible before starting the IEC 61850 configuration part.

Exporting SCD files

1.
Select the station in the Plant Structure view.
IEC 61850 communication engineering
SCD file
PCM 600 (3)
import SCD file
link GOOSE input data
Write to IED
IED 1
IED 2
IED n - 1
Section 7
IED n
77