Save the IED configuration migration report for later use as
PCM600 does not save it automatically.

Reengineering the migrated configuration

Reengineering in the Parameter Setting tool

Review the configuration migration report and update the function parameters
accordingly. Parameter values remain unchanged also for the functions not listed in
the migration report, that is, the functions that have the same version in both the
product versions.
Set the parameter values again for all the needed functions.
All functions listed in Obsolete Functions and Hardwares.
All parameters for which the migration failed. See the migration report for
failed parameters.
Note that some functions may have new settings.

Reengineering in the IEC 61850 Configuration tool

IEC 61850 data names have been changed in 2.0 compared to older product versions.
I CM automatically updates the names according to the new version names. Migration
report describes the details of the changes in dataset entries.
For the function block names in IEC 61850 Edition 1 and Edition 2,
see
Table

Reengineering in the Communication Management tool

Checking and updating Modbus points

If Modbus is used, the migrated Modbus point list should for most part correspond to
the configuration made in the old IED.
1.
Check the point list and verify that all the point types correspond to the old
configuration and Modbus master.
9.
Section 8
Configuration migration
91