Importing Scl Files To Pcm600 - ABB Relion 611 Series Engineering Manual

Hide thumbs Also See for Relion 611 Series:
Table of Contents

Advertisement

Section 7
IEC 61850 communication engineering
7.3.3
82

Importing SCL files to PCM600

The IED engineering tool must be able to receive an SCD file or an ICD file as an
import to receive the engineered communication extensions, for example, for the
different IEDs.
To be able to import an SCD file at station level, the option IED 61850 configuration
engineering mode enabled has to be cleared in PCM600.
1.
On the Tools menu, select Options and click IEC 61850 Configuration.
2.
Clear the option IED 61850 configuration engineering mode enabled and
click OK.
GUID-3C811FF5-97F7-4703-81EE-A0C4AC30C8D0 V1 EN
Figure 59:
Enabling SCD file import at station level
If the IED 61850 configuration engineering mode is enabled, SCD files cannot be
imported and an error message is shown.
GUID-68D1D489-27AC-4729-A887-DCE496CB48E0 V1 EN
Figure 60:
Error message when SCD files cannot be imported
1MRS241255 B
611 series
Engineering Manual