Working in the offline mode has an advantage compared to online mode in that the
preparation for the configuration can be started even though the protection relay is not
available.
1.
In the Plant Structure view, right-click the bay, point to New, point to the relay
application area such as Feeder IEDs and select the protection relay type to be
inserted.
Alternatively, drag an IED from the Object Types view to the
bay level.
2.
On the Configuration mode selection page, select Offline Configuration and
click Next.
Setting up an IED in the offline mode is similar as in the online mode; however,
with the offline mode it is not necessary to type the correct IP address in the
Communication port and IP address dialog box.
GUID-01675EF4-BA3B-4E90-A633-A99698D60E7E V1 EN
Figure 26:
Configuration mode selection wizard
3.
On the Order Code selection page, select the correct order codes and click
Next.
Section 4
Setting up a project
45