Inserting An Ied From The Template Directory - ABB Relion 611 Series Engineering Manual

Hide thumbs Also See for Relion 611 Series:
Table of Contents

Advertisement

Section 4
Setting up a project
4.3.3
46
Ensure that the order code is correct. PCM600 verifies later that
the order code matches with the relay. If the order code digits
related to the configuration, I/O or version do not match with the
relay, PCM600 does not allow writing the configuration to the
device. If other digits in the order code do not match, PCM600
informs about the mismatch with a dialog.
GUID-23DCA0B9-C3C7-45BC-9619-79E3B23EDA02 V1 EN
Figure 27:
Order code selection
4.
On the Version Selection page, select the IEC 61850 version and click Next to
generate the functions.
5.
The Setup Complete Page shows the summary of the IED type, version, IP
address and the selected order number. Click Finish to confirm the
configuration and conduct the insertion.

Inserting an IED from the template directory

IED templates can be used for replicating IEDs with same order code in PCM600
projects. Template includes IED configuration, communication protocol mappings
and parameters. An IED in the plant structure can be exported as a template (.pcmt
file). The template library can be built from all the exported IED templates.
It is also possible to insert an IED from the template library to create a new IED in the
plant structure. After a template IED has been imported, the IP address, the Caption
in IED's Object Properties and the Technical Key that corresponds to the physical
IED have to be changed.
1MRS241255 B
611 series
Engineering Manual