Standard Configuration Concept - ABB Relion 611 Series Engineering Manual

Hide thumbs Also See for Relion 611 Series:
Table of Contents

Advertisement

1MRS241255 B
2.2
611 series
Engineering Manual
All three parts require specific engineering and configuration.
A plant structure is used to identify each device in its location within the substation
organization. The plant structure is a logical image of the substation and the bays
within the substation. The organization structure for the devices may differ from the
structure of the primary equipment in the substation.
In PCM600 it is possible to set up a hierarchical structure of five levels for the device
identification.
Project
Substation = name of the substation
Voltage level = identifies to which grid type or part the device belongs in the
substation
Bay = bay within the voltage level
IED = the selection of the IED that is used in the bay; it is possible to insert several
IEDs within a bay, for example, one control device and two protection relays

Standard configuration concept

The product series covers protection relays developed for the protection of medium
voltage applications. Every product has predefined application-specific software
called standard configuration that contains protection, control, supervision and
measurement function blocks and default logical connections; for more information,
see the application manuals. The product also includes the standard configuration
specific default single-line diagram.
The standard configuration software consists of connections between an application's
functions developed according to the needs of a particular functional application. The
inputs and outputs are similarly assigned to a default set of connections such as
position indication and Master trip. The alarm LEDs are assigned to default
connections based on the order number.
Current and voltage channels for protection and measurement
functions are fixed as a part of standard configuration and cannot be
reassigned with Signal Matrix in PCM600.
The content of the standard configuration depends on the intended functional
application. The standard configurations also have selectable software options, which
are selected when ordering the protection relay. Some of the software options are
related to the protection relay hardware.
All functions and application logic included in a standard configuration of the
protection relay can be in use at the same time.
Relay engineering process
Section 2
15