Installing A Backup From An External Sd Card - Bosch Rexroth IndraControl XM42 Operating Instructions Manual

Table of Contents

Advertisement

IndraControl XM42 Controls
The operation mode switch SF1 provides the following options to open the
menu items:
1. Press SF1 < 3 seconds to the position "Clear": Menu item navigation and
selection.
Whenever SF1 is pressed, the next menu item is selected. (1 > 2 > 3 > 4 >
1 ...)
2. Press SF1 > 3 seconds to the position "Clear": Triggering the menu item
function.
The LED "E" changes from red to green.
Triggering the function is displayed by a brief switch-off and switch-on of
the respective LEDs.
3. To confirm the "Factory reset" (menu item no. 4), the operation mode
switch SF1 has to be set to the "Run" position.
The left column is flashing until the additional confirmation of the opera-
tion mode switch is on the "Run" position. The process of restoring the
state upon delivery is displayed by a running down of the right LED col-
umn. The completion of the restoration is displayed with a green LED "E".
The device must not be separated from the voltage supply during that time.
When selecting menu item 4 "Factory reset", all files on the XM4x
control installed since the commissioning are deleted. We recom-
mend to create a system firmware backup (see
"Firmware management" on page
The initial firmware is part of the hardware and not deleted.
After the system firmware has been loaded successfully, the control
does not boot the initial firmware anymore. To call the initial firm-
ware again, press the "Reset" button when switching on the 24 V
supply voltage until the LEDs DIA3 and DIA4 flash alternatingly in
red.

12.2.4 Installing a backup from an external SD card

If the control is as in delivery state, a backup can also be loaded to the control
without PC. Proceed as follows:
1. Copy a valid control backup to a Bosch Rexroth SD card (part no:
R911175017). Create a control backup using a PC with an SD card reader
or use the file manager of the First Touch commissioning tool.
2. Rename the image file to "system.fw".
3. Plug in the SD card to the base of the XM4x control labeled with "SD".
4. Switch off the 24 V supply voltage.
5. The initial firmware automatically starts the installation of the backup on
the control. While installing, the "ERR" LED is orange. After successful in-
stallation, the "ERR" LED is off and the "E" LED is green.
Device description
47) before using this function.
R911345566_Edition 03 Bosch Rexroth AG
43/65
chapter 12.3.3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents