8/65
Ambient conditions
Electrostatic discharge
ESD resistance acc. to DIN EN 61131-2
Test voltage
●
①
The vibration stress specifications assume the use of industrial-suited RJ-45 plug connec-
tions. The "Industrial RJ-45 plug" of the company Yamaichi is recommended (Y-Con-
Plug-41). The cables are available as accessories (RKB0020). To avoid vibration, secure
the cables using a short distance (< 20 cm). The USB interfaces XF30 and XF31 may only
be used up to a vibration stress of 1 g.
Tab. 6-1: Ambient conditions
NOTICE
The ambient air must not contain acids, alkaline solutions, corrosive agents,
●
salts, metal vapors and other electrically conductive contaminants in high
concentrations
The devices to be installed into the housing and installation compartments
●
must at least comply with the degree of protection IP 54 according to DIN EN
60529.
The device shall be provided in a suitable fire enclosure in the end-use appli-
●
cation.
NOTICE
Due to the risk of corrosion, avoid sulphurous gases (e.g. sulphur dioxide (SO
and hydrogen suphide (H
NOTICE
To avoid overheating and to ensure a smooth operation of the product according
to the minimum distances specified in
16, air has to circulate.
This is a product that corresponds to the limit values of the emitted
interference of class A (industrial environments), but not of class B
(residential area and small enterprises).
When using the product in residential areas or small enterprises, the
operator has to take actions to prevent radio interferences (also re-
fer to DIN EN 55022).
Bosch Rexroth AG R911345566_Edition 03
Criterion B
6 kV for contact discharge
8 kV for air discharge
Failure of the product due to contaminated air
Defective product due to gases jeopardizing
functions
S)). The product is not resistant against these gases.
2
Failure of the product due to overheating
chapter 10.1 "Installation notes" on page
IndraControl XM42 Controls
)
2