Updating The Initial Firmware - Bosch Rexroth IndraControl XM42 Operating Instructions Manual

Table of Contents

Advertisement

44/65
Device description
6. Use the "Reset" button to execute a reboot required to start the control
with system firmware.
The installation can be facilitated together with the "Backup system firmware"
function (see
chapter 12.3.3 "Firmware management" on page

12.2.5 Updating the initial firmware

Preparing data carriers
The initial firmware can be updated using either a USB stick or an SD card. For-
mat
the
data
(R911390383_XX_FWL -XM4200_INIT_-02VRS-_-_.fw) in the root directory of the
external data carrier.
Updating the initial firmware
Do not switch off the control while the update is running!
1. Plug the prepared data carrier (USB stick or SD card) into the switched-off
control (USB stick at the XF30, SD card at the XG10).
2. Switch on the 24 V supply voltage of the control. There are two different
variants:
1. If no system firmware is on the control upon delivery, the control direct-
ly boots the initial firmware and the commissioning tool "IndraControl
First Touch".
2. If there is a system firmware on the control, proceed as follows to go the
boot menu of the initial firmware:
2.1 Press the reset button SF2 when switching on the control and re-
lease the button only after the LEDs DIA3 and DIA4 flash alternating-
ly in red. The LED "E" is red.
2.2 Press "SF1" more than three seconds into the "Clear" position to
trigger the "Start FirstTouch" function. The LED "E" changes from red
to green.
3. The initial firmware updates automatically if a respective firmware file
(*.fw) is found on the external data carrier.
The control is restarted during the update.
The progress of the update is shown by the flashing of the LEDs "STA" or
"ERR".
4. The update is successfully completed if the right LED row is green.
5. Remove the external data carrier (USB stick or SD card) from the control.
6. Restart the control using the reset button "SF2" or interrupt the 24 V volt-
age supply briefly.
Bosch Rexroth AG R911345566_Edition 03
carrier
as
FAT
IndraControl XM42 Controls
or
FAT32.
Store
47).
the
firmware
file

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents