Front Side Connectors - ABB Relion 670 2.0 IEC Series Installation Manual

Protection and control
Table of Contents

Advertisement

Section 6
Connecting
6.1.1.2
38
Module
Serial SPA/LON/IEC 60870-5-103
communication modules (SLM)
Optical ethernet module (OEM)
mA input module (MIM)
GPS time synchronization module (GSM)
Static output module (SOM)
IRIG-B Time synchronization module (IRIG-B)

Front side connectors

GUID-D71BA06D-3769-4ACB-8A32-5D02EA473326 V1 EN
Figure 15:
RJ-45 communication port
1 IED serial communication port with RJ-45 connector
2 Green indicator LED (lit when the cable is successfully connected)
The cable between PC and the IED serial communication port shall be
a crossed-over Ethernet cable with RJ45 connectors. If the connection
are made via a hub or switch, a standard Ethernet cable can be used.
Description
Used for SPA/LON/IEC 60870–5–103
communication
PMC board for IEC 61850 based communication.
Analog input module with 6 independent,
galvanically separated channels.
Used to provide the IED with GPS time
synchronization.
Module with 6 fast static outputs and 6 change over
output relays.
Module with 2 inputs. One is used for handling both
pulse-width modulated signals and amplitude
modulated signals and one is used for optical input
type ST for PPS time synchronization.
1MRK514019-UEN A
670 series 2.0 IEC
Installation manual

Advertisement

Table of Contents
loading

Table of Contents