1MRS757183 F
3.2.4.5
PML630/Compact Load-Shedding Solution
Operation Manual
OFF, load shed functionality cannot be active. Fast load shed functionality is active
only if LSCACLS (core) function's Operation is set in ON mode.
If fast load-shedding is blocked, slow load-shedding is also blocked automatically.
However, manual load-shedding is independent and can be operated even when fast
and slow load-shedding modes are blocked.
Three out of the five functional keys in the LHMI can be configured (see the
engineering manual).
1
2
3
4
5
GUID-0FC3380C-F683-4F7C-9B19-D987C3604797 V3 EN
Figure 9:
Load-shedding functional keys
1 Load-shedding blocked
2 Slow load-shedding blocked
3 Spare
4 Spare
5 Global load-shedding reset
Front communication
The RJ-45 port in the LHMI enables front communication.
Section 3
IED Overview