Installation Recommendations; Configurations; Horizontal Configuration - Sears GT Series Installation Instructions Manual

Geothermal
Table of Contents

Advertisement

INSTALLATION
RECOMMENDATIONS
The
Water-to-Air
Heat
Pumps
are
designed
to operate
with
entering
fluid temperature
between
20°F
to 90°F
in the heating
mode and between
30°F to 120°F
in the cooling
mode.
NOTE:
50 ° minimum
Entering
Water
Temperature
(EWT)
is
recommended
for well
water
applications
with
sufficient
water
flow to prevent
freezing.
Antifreeze
solution
is required
for all
closed
loop
applications
or
EWT
less
than
45 ° . Cooling
Tower/Boiler
and Geothermal
applications
should
have sufficient
antifreeze
solution
to
protect
against
extreme
conditions
and
equipment
failure.
Frozen
water
coils
are
not
covered
under
warranty.
Other
equivalent
methods
of temperature
control
are
acceptable.
Check
Equipment
and Job Site
Movin_ and Storage
If the equipment
is not needed
for immediate
installation
upon its
arrival
at the job site, it should
be left in its shipping
carton
and
stored in a clean, dry area. []nits must
only be stored or moved
in
the normal
upright
position
as indicated
by the "UP"
arrows
on
each carton
at all times.
CONFIGURATIONS
Horizontal
Configuration
The Horizontal
Configuration
water source
heat pump
is designed
to have a field configurable
blower
orientation:
end blow (default)
and straight
through.
(See Fig. 4 and Fig. 5)
A14034
Fig. 4 - End
Blow Configuration
(default)
EQUIPMENT
DAMAGE
HAZARD
Failure
to follow this caution
may result in equipment
damage.
If unit stacking
is required
for storage,
stack units as follows:
Do not stack
units larger
than 6 tons!
Vertical
units:
less
than
6 tons,
no
more
than
two
high.
Horizontals
units: less than 6 tons, no more than three high.
Inspect Equipment
Be certain to inspect all cartons
or crates on each unit as received
at
the job site before signing
the freight bill. Verify that all items have
been
received
and
that there
are no visible
damages;
note
any
shortages
or damages
on all copies of the freight bill. In the event
of damage
or shortage,
remember
that the purchaser
is responsible
for filing the necessary
claims with the carrier. Concealed
damages
not discovered
until after removing
the units
from the packaging
must be reported
to the carrier within
24 hours
of receipt.
Location
/ Clearance
Locate
the unit in an indoor
area that allows
easy removal
of the
filter and access panels,
and has enough
room for service personnel
to perform
maintenance
or repair. Provide
sufficient
room to make
fluid, electrical,
and duct connection(s).
If the unit is located
in a
confined
space such as a closet, provisions
must be made for return
air to freely
enter the face of unit's
air coil. On horizontal
units,
allow adequate
room below the unit for a condensate
drain trap and
do not locate the unit above supply piping.
[]NIT
OPERATION
HAZARD
Failure
to follow
this caution
may
result
in equipment
damage
or improper
operation.
These
units
are
not
approved
for
outdoor
installation;
therefore,
they must be installed
inside the structure
being
conditioned.
Do
not locate
in areas
that
are subject
to
freezing.
A14035
Fig. 5 - Straight
Through
Configuration
NOTE:
Left-hand
and Right-hand
horizontal
(HZ)
units
have
different
Blower
Configuration
instructions.
Be sure ro refer to the
correct
instructions
in this document
for the proper
installation
for
each configuration.
NOTE:
Internally
mounted
electric
heat is available
in end blow
configurations
only.
NOTE:
Blower
configuration
changes
should
be done
prior
to
unit being installed
in the final location.
[]NIT
OPERATION
HAZARD
Failure
to follow
this caution
may
result
in equipment
damage
or improper
operation.
Discharge
air configuration
change is not possible
on Heat
Pumps
equipped
with Electric
Heat Option.
REQUIRED TOOLS:
• 5/16" hex head screwdriver
• 3/8" hex head screwdriver
• 7/16" hex head screwdriver
• Flat screwdriver
• Phillips
head screwdriver
• 1/4" hex head screwdriver
• Needle nose pliers
• 5/16"
- 1/4" ratchet wrench

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gt024Gt036Gt048Gt060Gt072

Table of Contents