Sears GT Series Installation Instructions Manual page 34

Geothermal
Table of Contents

Advertisement

UNIT S HORT
Unit o versized
Recalculate
heating and orcooling loads.
CYCLES
Thermostat
Thermostat
installed near asupply airgrill; r elocate thermostat.
Readjust
heat a nticipator.
Wiring a nd
Check fordefective orimproperly
calibrated low pressure
switch.
controls
INSUFFICIENT Unit u ndersized Recalculate
heating and orcooling loads. Ifexcessive,
possibly adding
COOLING
OR
insulation and shading will
r ectify the problem
HEATING
Loss of
Check for leaks in duct work or introduction
of ambient
air through
conditioned
air by
doors or windows
leakage
Airflow
Lack of adequate
air flow or improper
distribution
of air. Replace dirty
Refrigerant
Low on refrigerant
charge causing inemcient
operation
charge
Compressor
Check for defective
compressor,
if discharge
is too low and suction
pressure is too high, compressor
is not pumping
properly.
Replace
compressor.
Reversing Valve
Defective
reversing valve creating
bypass of refrigerant
from discharge
of suction side of compressor.
Replace reversing valve
Operating
Compare
unit operation
pressures to the pressure/temperature
chart
pressures
for the unit.
TXV
Check TXV for possible restriction
or defect. Replace if necessary.
Moisture,
The refrigerant
system may be contaminated
with moisture
or
noncondensables
noncondensables.
Reclaim refrigerant,
replace filter dryer, evacuate
the
refrigerant
system, and recharge
with factory recommended
charge.
34